Consider the Trane Comm3/Comm4 bridge as if it is a Trane BCU. See the help section Scanning a Trane Tracer Summit Network. When a BACnet scan is performed on the SC network, the Trane Comm3/Comm4 Bridge will appear as a BACnet device typically in the device ID range of 100-200. Scan the Trane Comm 3-4 Bridge and mark the Sub-device checkbox.
To allow a Connect Mini Agent MiniAgent to retrieve LON/Comm5 data from the Tracer SC, the Tracer SC database will need to be created within the Connect Gateway Manager Tool. This Gateway parses LON/Comm5 objects within a Trane Tracer SC and creates BACnet virtual devices for all devices stored within the Tracer SC controller. This allows the Trane LON/Comm5 devices communicating to the Tracer SC to appear in Connect as multiple BACnet virtual devices.
To allow a Connect Mini Agent MiniAgent to retrieve data from the Tracer SC, the Tracer SC database will need to be created within the Connect Gateway Manager Tool. This Gateway parses the objects within a Trane Tracer SC and creates BACnet virtual devices for all devices stored within the Tracer SC controller. This allows the Trane Comm 4 and Comm 5 devices communicating to the Tracer SC to appear in Connect as multiple BACnet virtual devices.
...