To allow a Connect Mini Agent MiniAgent to retrieve data from the Siemens Insight Server, the Siemens Insight Gateway parses the objects within a Siemens Insight Server and creates BACnet virtual devices for all devices stored within the Siemens Insight server. This allows the Siemens devices communicating to the Siemens Insight server to appear in Connect as multiple BACnet virtual devices.

  1. Navigate to the Connect Gateway Manager located at C:\Program Files (x86)\KEY2ACT\Connect2018 and double-click to launch. 

    expand

    Image Removed

  2. Choose New Gateway

    ExpandImage Removed

  3. Choose OK.
  4. In the Database Type window, choose Siemens Insight and choose OK

    ExpandImage Removed

  5. Name the new database and choose Save

    Expand

    Image Removed

  6. Choose BACnet Settings

    Expand

    Image Removed

  7. Choose a unique BACnet device ID for this site (default is 70). 

    note

    Device IDs must be unique.

  8. Choose BACnet IP Settings.
  9. Enter the address of the Insight Server.
  10. Choose OK.
  11. Choose Scan Network. Then Scan Network again.
  12. Choose the device range and where to scan for the object name (usually scanning by name returns the desired result) and choose OK

    Expand

    Image Removed

  13. After the scan completes, choose the devices with objects that will be trended. choose Save and Close.
  14. Close the Gateway Manager and open Connect.
  15. Go to Configuration Explorer and choose the Agent that was previously created.
  16. Choose Properties.
  17. Choose Edit to the right of the Connection field.
  18. Choose Advanced and choose Import Gateway.
  19. Choose the gateway that was created.
  20. Choose OK then choose OK again.
  21. Choose the Home Image Removed icon, choose the Agent, and then choose Restart

    Expand

    Image Removed

  22. Choose the Configuration Explorer Image Removed icon and choose your Agent.
  23. Choose Scan Network, choose Scan Network, and then choose OK

    ExpandImage Removed

  24. The result should have BACnet virtual devices created from the Gateway Manager.
  25. Choose Save and Close.