WennSoft has predefined sensor calculations to choose from when creating your calculated sensors.

NameFormula
Cooling Air Temperature DeviationCooling Air Temperature Setpoint - Cooling Air Temperature
Chilled Water Approach

(Evaporator Leaving Water Temperature) – (Evaporator Saturated Refrigerant Temperature)

Condenser Water Approach

(Condenser Saturated Refrigerant Temperature) – (Condenser Leaving Water Temperature)

Chilled Water Delta T

(Evaporator Entering Water Temp) – (Evaporator Leaving Water Temp)

Condenser Water Delta T

(Condenser Leaving Water Temp) – (Condenser Entering Water Temp)

Differential Steam Pressure Deviation(abs(Differential Steam Pressure Setpoint - Differential Steam Pressure) / max(0.1, Differential Steam Pressure Setpoint)) * 100
Differential Water Pressure Deviation(abs(Differential Water Pressure Setpoint - Differential Steam Pressure) / max(0.1, Differential Water Pressure Setpoint)) * 100
Heating Air Temperature DeviationHeating Air Temperature Setpoint - Heating Air Temperature
Outside Air Dewpoint

Celcius to Celsius Formula
Ts = (243.04 × ln(RH / 100) + 17.625 T/(243.04  + T)) / (17.625 - ln(RH / 100) + 17.625 T/(243.04+T))

Fahrenheit to Fahrenheit Formula
Ts = [ (243.04 × ln(RH / 100) + 17.625 * ((T - 32) * 5/9)/( 243.04  + ((T - 32) * 5/9)) ) / (17.625 - ln(RH / 100) + 17.625 * ((T - 32) * 5/9)/(243.04 + ((T - 32) * 5/9))) ] * 9/5 + 32

Fahrenheit to Celcius Formula
Ts = (243.04 × ln(RH / 100) + 17.625 * ((T - 32) * 5/9)/( 243.04  + ((T - 32) * 5/9)) ) / (17.625 - ln(RH / 100) + 17.625 * ((T - 32) * 5/9)/(243.04 + ((T - 32) * 5/9)))

T: Outside Air temperature
RH: Outside Air Relative Humidity

T and RH are existing sensors.

Outside Air Wet Bulb

Celcius to Celsius Formula
Tw ​= T arctan(0.151977 (RH + 8.313659)1/2) + arctan(T + RH) − arctan(RH − 1.676331) + 0.00391838(RH)3/2arctan(0.023101RH) − 4.686035

Fahrenheit to Fahrenheit Formula
Tw ​= [ ((T - 32) * 5/9) * arctan(0.151977 (RH + 8.313659)1/2) + arctan( ((T - 32) * 5/9) + RH) − arctan(RH − 1.676331) + 0.00391838(RH)3/2arctan(0.023101RH) − 4.686035 ] * 9/5 + 32

Fahrenheit to Celcius Formula
Tw ​= ((T - 32) * 5/9) * arctan(0.151977 (RH + 8.313659)1/2) + arctan( ((T - 32) * 5/9) + RH) − arctan(RH − 1.676331) + 0.00391838(RH)3/2arctan(0.023101RH) − 4.686035 

T: Outside Air temperature
RH: Outside Air Relative Humidity

T and RH are existing sensors.

PowerCurrent * Voltage
Power (kVa) *coming soonPower + Power + Power + Power
Primary Differential Water Pressure Deviation(abs(Primary Differential Water Pressure Setpoint - Primary Differential Water Pressure) / max(0.1, Primary Differential Water Pressure Setpoint)) * 100
Primary Supply Water TemperaturePrimary Supply Water Temperature Setpoint - Primary Supply Water Temperature
Secondary Differential Water Pressure Deviation(abs(Secondary Differential Water Pressure Setpoint - Secondary Differential Water Pressure) / max(0.1, Secondary Differential Water Pressure Setpoint)) * 100
Secondary Supply Water Temperature DeviationSecondary Supply Water Temperature Setpoint - Secondary Supply Water Temperature
Space Air CO DeviationSpace Air CO Setpoint - Space Air CO
Space Air CO2 DeviationSpace Air CO2 Setpoint - Space Air CO2
Space Air DewpointSpace Air Temperature(C) - ((100 - Space Air Relative Humidity) / 5)
Space Air Methane DeviationSpace Air Methane Setpoint - Space Air Methane
Space Air PM2.5 DeviationSpace Air PM2.5 Setpoint - Space Air PM2.5
Space Air Relative Humidity DeviationSpace Air Relative Humidity Setpoint - Space Air Relative Humidity
Space Air Temperature DeviationSpace Air Temperature Setpoint - Space Air Temperature
Space Air TVOC DeviationSpace Air TVOC Setpoint - Space Air TVOC
Supply Air Flow Deviation(abs(Supply Air Flow Setpoint - Supply Air Flow) / max(0.1, Supply Air Flow Setpoint)) * 100
Supply Air Pressure Deviation(abs(Supply Air Pressure Setpoint - Supply Air Pressure) / max(0.1, Supply Air Pressure Setpoint)) * 100
Supply Air Temperature DeviationSupply Air Temperature - Supply Air Temperature Setpoint
Supply Water Flow Deviation(abs(Supply Water Flow Setpoint - Supply Water Flow) / max(0.1, Supply Water Flow Setpoint)) * 100
Supply Water Temperature DeviationSupply Water Temperature Setpoint - Supply Water Temperature
Total RuntimeSum of Time for time given for a True condition.