The Trane Tracer SC system controller (Tracer  SC) is used when LON/Comm5 devices are connected to an SC.

The Trane Tracer SC gateway is not required to retrieve BACnet data from:

  • BACnet MSTP devices connected under a Tracer SC.
  • Trane Comm3 or Comm 4 devices connected under a Trane Comm3/Comm4 bridge. The Trane Comm3/Comm4 bridge parses Comm3/Comm4 objects within a Trane Tracer SC and creates BACnet virtual devices for all.

Consider the Trane Comm3/Comm4 bridge as if it is a Trane BCU. See the help section Scanning a Trane Tracer Summit Network. When a BACnet scan is performed on the SC network, the Trane Comm3/Comm4 Bridge will appear as a BACnet device typically in the device ID range of 100-200. Scan the Trane Comm 3-4 Bridge and mark the Sub-device checkbox.

To allow a Connect MiniAgent to retrieve LON/Comm5 data from the Tracer SC, the Tracer SC database will need to be created within the Connect Gateway Manager Tool. This Gateway parses LON/Comm5 objects within a Trane Tracer SC and creates BACnet virtual devices for all devices stored within the Tracer SC controller. This allows the Trane LON/Comm5 devices communicating to the Tracer SC to appear in Connect as multiple BACnet virtual devices.

To allow a Connect MiniAgent to retrieve data from the Tracer SC, the Tracer SC database will need to be created within the Connect Gateway Manager Tool. This Gateway parses the objects within a Trane Tracer SC and creates BACnet virtual devices for all devices stored within the Tracer SC controller. This allows the Trane Comm 4 and Comm 5 devices communicating to the Tracer SC to appear in Connect as multiple BACnet virtual devices.


To configure a Trane Tracer SC gateway:

  1. Navigate to the Connect Gateway Manager located at C:\Program Files (x86)\KEY2ACT\Connect2018 and double-click to launch. 

     Click here to expand...

  2. Choose New Gateway.
  3. Choose OK.
  4. In the Database Type window, choose Trane Tracer SC Gateway and then choose OK. 

     Click here to expand...

  5. Name the new database and choose Save.
  6. Choose BACnet settings

     Click here to expand...

  7. Choose Scan Network then choose Scan Network again.
  8. Choose device range and where to scan for the object name (usually scanning by name returns desired result) and choose OK.
  9. After the scan completes, choose the devices with objects that will be trended and choose Save and Close.
  10. Close the Gateway Manager and open Connect.
  11. Go to Configuration Explorer and choose the Agent that was previously created.
  12. Choose Properties.
  13. Choose Edit next to Connection.
  14. Choose Gateway and choose Import Gateway.
  15. Choose the gateway that was created.
  16. Choose OK then choose OK again.
  17. Choose the Home  icon, choose the Agent, and then choose Restart

     Click here to expand...

  18. Choose the Configuration Explorer  icon and choose your Agent.
  19. Choose Scan Network, then choose Scan Network, and then choose OK. The result should have BACnet virtual devices created from the Gateway Manager. 

     Click here to expand...

  20. Choose the devices with objects that will be trended and choose Save and Close.