Navigate to the Connect Gateway Manager located at C:\Program Files (x86)\KEY2ACT\Connect2018 and double-click to launch.
Expand Choose New Gateway.
expand- Choose OK.
In the Database Type window, choose Siemens Insight and choose OK.
Expand Name the new database and choose Save.
Expand Choose BACnet Settings.
Expand Choose a unique BACnet device ID for this site (default is 70).
noteDevice IDs must be unique.- Choose BACnet IP Settings.
- Enter the address of the Insight Server.
- Choose OK.
- Choose Scan Network. Then Scan Network again.
Choose the device range and where to scan for the object name (usually scanning by name returns the desired result) and choose OK.
expand- After the scan completes, choose the devices with objects that will be trended. choose Save and Close.
- Close the Gateway Manager and open Connect.
- Go to Configuration Explorer and choose the Agent that was previously created.
- Choose Properties.
- Choose Edit to the right of the Connection field.
- Choose Advanced and choose Import Gateway.
- Choose the gateway that was created.
- Choose OK then choose OK again.
Choose the Home icon, choose the Agent, and then choose Restart.
expand- Choose the Configuration Explorer icon and choose your Agent.
Choose Scan Network, choose Scan Network, and then choose OK.
Expand - The result should have BACnet virtual devices created from the Gateway Manager.
- Choose Save and Close.